FreeNo Sign-upUpdated 2026

Radiator BTU Calculator

Find the exact BTU output for your radiator — or calculate how much BTU your room needs. Supports panel, column, cast iron & electric with ΔT correction.

  • Panel radiator BTU output by size (Type 11, 21, 22)
  • Column & cast iron BTU per section
  • ΔT50, ΔT40, ΔT30 correction — heat pump ready
  • Room BTU requirement calculator
  • UK metric (mm/m²) & imperial (in/sq ft) supported

⚡ Quick Radiator BTU Estimator

Watts:
kW:
Coverage:

Detailed Radiator BTU Calculators

Two modes — find your radiator's actual output, or calculate exactly what your room needs.

🌡️BTU Output Calculator (By Radiator Size)

Enter radiator dimensions and type to calculate heat output at any system temperature.

BTU/hr
Watts
kW

🏠BTU Needed Calculator (By Room)

Calculate total heat output required for your room and get a recommended radiator size.

BTU Needed
Watts
Radiator Size

All Radiator BTU Calculators

Each radiator type uses a different BTU formula. Each calculator uses specialised formulas for accurate sizing.

🔲

Panel Radiator BTU Calculator

Single panel (Type 11), double panel (Type 21), and double panel double convector (Type 22/K2). The most common radiator type in UK and European homes.

TYPE 11TYPE 21TYPE 22ΔT50
🏛️

Column Radiator BTU Calculator

2, 3, and 4-column radiators. BTU calculated from column count × height × width. Popular for period properties and vertical spaces.

2-COLUMN3-COLUMN4-COLUMN
⚙️

Cast Iron Radiator BTU Calculator

Per-section BTU calculation for antique and reproduction cast iron radiators. Higher thermal mass than steel — slower heat-up, longer heat retention.

PER SECTION660 MM760 MM

Electric Radiator BTU Calculator

Converts rated wattage to BTU output. 1 watt = 3.412 BTU/hr. Compare electric vs. hydronic radiators for the same room size.

WATTAGE → BTUkW → BTU
📏

Rad BTU Calculator (Size Only)

Enter height and width in mm — no model needed. Uses EN 442 standard output coefficients for a fast estimate directly from radiator dimensions.

EN 442MM → BTUFAST
🌊

Baseboard Radiator BTU Calculator

Linear BTU output per metre or foot for hydronic baseboard radiators. Common in North American homes and renovated UK properties.

PER METREPER FOOTHYDRONIC

How to Calculate Radiator BTU

Step 1 — Calculate Room Heat Loss

The BTU your room needs depends on volume, insulation, windows, and external walls. Start with this formula:

BTU Required = Room Volume (ft³) × Heat Loss Factor
Insulation LevelBTU per ft³W per m³
Poor (solid walls, single glazing)5–658–70
Average (cavity walls, double glazing)3–435–46
Good (insulated, double glazing)2–323–35
Excellent (new build, triple glazing)1.5–217–23

Step 2 — Convert BTU to Watts

Watts = BTU/hr ÷ 3.412

UK radiator manufacturers publish output in watts at ΔT50. Use watts when browsing radiator catalogues or comparing products.

Step 3 — Apply ΔT Correction Factor

If your system runs at a different temperature from the rated ΔT50, multiply the radiator's rated output by the correction factor:

ΔT60
×1.264
Old high-temp boiler
ΔT50
×1.000
Standard rated output
ΔT40
×0.737
Modern condensing boiler
ΔT30
×0.518
Heat pump compatible
ΔT20
×0.306
Low-temp heat pump

Example: A radiator rated 4,000 BTU at ΔT50 will only output 2,072 BTU at ΔT30 when connected to a heat pump.

Key Radiator Sizing Rules

  • 1UK standard: 60 W (205 BTU) per m² for well-insulated rooms at ΔT50
  • 2Older/poor insulation homes: 80–100 W per m²
  • 3Bathrooms: Add 10–15% extra for humidity-related heat loss
  • 4Heat pump systems (ΔT30): Size radiators ~2× larger than for a gas boiler
  • 5North-facing rooms: Add 5–10% for reduced solar gain

Panel Radiator BTU Output by Size (2026)

Type 22 (K2) double panel double convector at ΔT50 — the most popular radiator type in UK homes.

Radiator Size (H × W) Watts (ΔT50) BTU/hr (ΔT50) Watts at ΔT40 Watts at ΔT30 Room Coverage
300 × 400 mm349 W1,191 BTU257 W181 W≤ 4 m²
300 × 800 mm698 W2,381 BTU514 W361 W≤ 8 m²
400 × 600 mm668 W2,280 BTU492 W346 W≤ 8 m²
500 × 600 mm851 W2,904 BTU627 W441 W≤ 10 m²
600 × 600 mm1,022 W3,488 BTU753 W529 W≤ 12 m²
600 × 800 mm1,362 W4,649 BTU1,004 W706 W≤ 16 m²
600 × 1000 mm1,703 W5,811 BTU1,255 W882 W≤ 20 m²
600 × 1200 mm2,044 W6,974 BTU1,506 W1,059 W≤ 24 m²
600 × 1600 mm2,725 W9,299 BTU2,008 W1,411 W≤ 32 m²
700 × 1400 mm2,828 W9,650 BTU2,084 W1,465 W≤ 33 m²

* Type 22 at ΔT50 (mean water temp 70°C, room 20°C). Room coverage assumes 60 W/m² average insulation.

Cast Iron Radiator BTU Per Section

Column Type / HeightBTU per SectionWatts per Section10-Section Total
4-column, 660 mm~580 BTU~170 W5,800 BTU / 1,700 W
4-column, 760 mm~665 BTU~195 W6,650 BTU / 1,950 W
3-column, 760 mm~512 BTU~150 W5,120 BTU / 1,500 W
2-column, 960 mm~450 BTU~132 W4,500 BTU / 1,320 W

Radiator BTU Calculator — Frequently Asked Questions

Direct answers to the most common radiator sizing questions.

For panel radiators, measure height and width in mm and reference the manufacturer's output table at ΔT50. A 600×1000 mm Type 22 panel radiator produces approximately 5,800 BTU/hr (1,703 W) at ΔT50. Use our calculator above for instant results from any dimensions.

ΔT50 (Delta T 50) means the mean water temperature in the radiator is 50°C above room temperature — typically a flow/return of 75°C/65°C with a room at 20°C. This is the standard EN 442 test condition for all UK and European radiator BTU ratings.

Yes. Heat pumps run at lower flow temperatures (ΔT30–ΔT35), which reduces radiator output significantly. A radiator rated 6,000 BTU at ΔT50 only delivers around 3,108 BTU at ΔT30 (×0.518 factor). Plan to use approximately 2× the radiator size compared to a gas boiler system.

A standard 4-column 760 mm cast iron radiator produces approximately 665 BTU (195 W) per section at ΔT50. Multiply by your total section count. Cast iron has higher thermal mass than steel — it heats more slowly but retains heat longer after the boiler cycles off.

Both measure heat output. 1 watt = 3.412 BTU/hr. UK manufacturers publish in watts; US manufacturers in BTU/hr. To convert: BTU/hr ÷ 3.412 = Watts, or Watts × 3.412 = BTU/hr.

The UK standard is 60 W (205 BTU) per m² for average insulation at ΔT50. For poorly insulated older homes use 80–100 W/m². New builds with excellent insulation typically need 40–55 W/m². Always add 10–15% extra for bathrooms.

For a 15 m² room with average insulation at ΔT50, you need approximately 900 W (3,070 BTU). A 600×600 mm Type 22 (1,022 W) covers this comfortably. Use the room calculator above for a precise result based on your ceiling height and insulation type.

More BTU Calculators

📐

EN 442 & CIBSE Standards

Radiator output formulas based on EN 442 European test standard and CIBSE heat loss methodology used by UK heating engineers.

🔒

Instant, Private Results

All calculations run in your browser. No account, no data stored, works offline on any device.

📱

Mobile-Optimised

Use it at the radiator showroom or at home. Fully responsive on all screen sizes.

Authoritative HVAC References
BEAMA / BSRIA
EN 442 Radiator Standards
European standard test conditions for radiator heat output at ΔT50.
↗ beama.org.uk
CIBSE
Heat Loss Calculations
CIBSE Guide A: Environmental Design — the standard for UK heat loss calculations.
↗ cibse.org
Energy Saving Trust
Heat Pump Guidance
Guidance on sizing radiators for low-temperature heat pump systems.
↗ energysavingtrust.org.uk
ASHRAE
ASHRAE Standards
Technical HVAC engineering standards used worldwide for load calculations.
↗ ashrae.org